<ins id="60n1a"><optgroup id="60n1a"><menuitem id="60n1a"></menuitem></optgroup></ins>
    <samp id="60n1a"><tfoot id="60n1a"></tfoot></samp>
    <fieldset id="60n1a"><table id="60n1a"><kbd id="60n1a"></kbd></table></fieldset>
  • 
    
    <samp id="60n1a"></samp>
    <samp id="60n1a"></samp>
  • <fieldset id="60n1a"><table id="60n1a"></table></fieldset>
    Loading...

    XK-12 box type opening and closing station
    Category:High voltage switchgear
    Release date:2019-02-26 16:02:11
     
    KYN28A-12 Installation Instructions
    1 Overview
    KYN28A-12 indoor metal armored central switchgear (hereinafter referred to as switchgear) is the latest generation of three-phase AC 50Hz, 3~12KV single busbar segmentation system developed by Tianshun Electric Co., Ltd. It is mainly used in power distribution systems of power plants, substations, industrial and mining enterprises, residential quarters, high-rise buildings, schools, etc., as a means of receiving and distributing electrical energy, and has functions of controlling, protecting and monitoring circuits. This type of relay chamber panel can be installed with various types of microcomputer-type integrated relay protection devices, which can realize intelligent control of the system. It has remote control, telemetry, remote signaling and remote adjustment functions. It is controlled by CAN bus with communication interface. Field network. It also has the function of preventing accidental operation of the circuit breaker, preventing the push and pull of the load, preventing the grounding switch from being charged, preventing the grounding switch from being powered at the grounding position, and preventing the accidental charging interval, that is, the "five-proof" function. The switchgear can be equipped with VS1, VD4, VB2 and other series of vacuum circuit breakers.

    2. The external dimensions and weight of the equipment are shown in Table 1 and Figure 1.


    Table 1

    Height H (mm) 2300(2200)
     Width W (mm) Branch busbar rated current up to 1250A, thermal stable current 40kA 800
    Branch busbar rated current 1600A and above 1000
    Depth D (mm) Cable entry and exit line 1500
    Overhead access line 1660
    Weight (kg) 700~1200

     

    Serial number project 單位 data
    1 Rated voltage kV 12
    2 Rated insulation level 1min power frequency withstand voltage kV 42
    Lightning impulse withstand voltage kV 75
    3 Rated frequency Hz 50
    4 Main busbar rated current A 630,1250,1600,2000,2500,3150,4000
    5 Branch busbar rated current A 630,1250,1600,2000,2500,3150,4000
    6 4s thermal stable current (effective value) kA 16,20,25,31.5,40,50
    7 Rated dynamic stability current (peak)* kA 40,50,63,80,100,125
    8 Protection level   The enclosure is IP4X; the compartment and circuit breaker door are IP2X when opened

    Note: * The short circuit capacity of the current transformer should be considered separately.

    ? Technical parameters of vacuum circuit breaker

     

    Serial number name unit Parameter
    1 Rated voltage kV 12
    2 Rated frequency Hz 50
    3 Rated current A 630
    1250
    630
    1250
    1250
    1600
    2000
    2500
    3150
    1250
    1600
    2000
    2500
    3150
    4 Rated short-circuit breaking current kA 20 25 31.5 40
    5 Rated short-circuit withstand current 20 25 31.5 40
    6 Rated short circuit duration S 4
    7 Rated peak withstand current kA 50 63 80 100
    8 Rated short circuit closing current 50 63 80 100
    9 Rated insulation level 1min power frequency withstand voltage kV 42
    Lightning impulse withstand voltage 75
    10 Secondary circuit power frequency withstand voltage (1min) V 2000
    11 Rated operation sequence   O-0.3s-CO-180s-CO(小于40kA)
    O-180s-CO-180s-CO(40kA)
    12 Mechanical life M2級(10000)
    13 Operating mechanism Energy storage motor Rated voltage V AC110/220DC110/220
    Energy storage time s ≤15
    Closing trip coil Rated voltage V AC110/220DC110/220
    14 Contact opening distance mm 11±1
    15 Contact stroke 3.5±0.5
    16 Three-phase tripping synchronization ms ≤2
    17 Contact closing bounce time ≤2
    18 Contact closing contact pressure N 2000±200 (20kA)
    2400±200 (25kA)
    3100±200 (31.5kA)
    4750±250 (40kA)
    19 Average opening speed m/s 0.9~1.2
    20 Average closing speed 0.5~0.8
    21 Opening time (at rated operating voltage) ms 20~55
    22 Closing time (at rated operating voltage) 35~70
    23 Conductive loop resistance μΩ ≤65(630A)
    ≤55(1250A)
    ≤35(1600A~2000A)
    ≤25(2500A及以上)

    Note: 1. The average opening speed refers to the average speed of the circuit breaker contact just after 6mm;
    2. The average closing speed refers to the average speed of the full opening distance of the circuit breaker.

    4. Structure
    The equipment is designed according to the armored metal-enclosed switchgear in GB3906. The whole body is composed of two parts: the cabinet and the middle-mounted removable parts (ie, the handcart), as shown in Figure 2. The cabinet is divided into four separate compartments, the enclosure is IP4X, and the protection level is IP2X when the compartments and circuit breaker compartments are open. With overhead access lines, cable access lines and other functional solutions, the switch cabinets of each solution can be arranged to form a power distribution device capable of designing functions according to the application. The unit can be installed, commissioned and maintained from the front, so it can be stacked back-to-back or wall-mounted, increasing equipment safety, flexiblity and floor space

     



     

    Figure 2 Grounding diagram of switchgear

    Table 4

    Cabinet width A (mm) use 柜體深度L(mm)
    800 Cable entry and exit line 1500
    Overhead access line 1660
    1000 Cable entry and exit line 1500
    Overhead access line 1660


     

     

    客服中心
    工作時間

    周一至周日

    8:00 - 18:00

    點擊這里給我發(fā)消息 銷售客服


    請直接QQ聯(lián)系!
    展開客服
    免费人成激情视频在线观看冫,AV无码国产淫穴高清一区二区三区,国产三级在线观看完整版,永久在线无码免费网站
    <ins id="60n1a"><optgroup id="60n1a"><menuitem id="60n1a"></menuitem></optgroup></ins>
      <samp id="60n1a"><tfoot id="60n1a"></tfoot></samp>
      <fieldset id="60n1a"><table id="60n1a"><kbd id="60n1a"></kbd></table></fieldset>
    • 
      
      <samp id="60n1a"></samp>
      <samp id="60n1a"></samp>
    • <fieldset id="60n1a"><table id="60n1a"></table></fieldset>